Trade Websites   Home    Latest TradeLeadsHelp   Add to favorite
Log In | Log Out | My Account | Register(free) |
Home   > Industrial Supplies   > Air Treatment & Conditioning   >
Post New TradeLead

ground source heat pump

ground source heat pump


Detailed Description


Heating, cooling and domestic hot water;
Adopt Siemens controller, easily understandable control simplifies;
Internal soft start for single phase units;
Electric heater is optional
Scroll compressor;
Plate type heat exchanger;



Geothermal Heat Pump with cooling

Heat pump
Type
GSWW8/B
GSWW10/B
GSWW13/B
GSWW15/B
GSWW20/B
GSWW26/B
GSWW30/B

Dimensions,weights,connection dimensions

Dimensions
HxWxD
960x600X600
960x800X600

Weight
kg
105
110
120
130
180
195
210

Refrigerant
Type
R407C

Filling weight
kg
2
2.3
2.5
2.8
4
4.5
5

Permissible operating pressure
Mpa
3
3
3
3
3
3
3

Pipe connector-hot side
Inch
G1”
G1”
G11/4”
G11/4”
G11/2”
G11/2”
G11/2”

Pipe connector-cold side
Inch
G1”
G1”
G11/4”
G11/4”
G11/2”
G11/2”
G11/2”

Evaporator
Type
Brazed plate heat exchanger

Condenser
Type
Brazed plate heat exchanger

Compressor
  1xScroll
1xScroll
1xScroll
1xScroll
2xScroll
2xScroll
2xScroll

Performance Heat pump

Heat output
at B0/
W35(1)
kW
8
10.2
13.1
15.5
20
26
30.5

Power consumption
kW
1.9
2.36
2.95
3.53
4.45
5.8
6.85

Performance factor
4.21
4.32
4.44
4.39
4.49
4.48
4.45

Inside volume flow(3)
m3/h
1.4
1.75
2.25
2.67
3.44
4.5
5.2

Outside volume flow(4)
m3/h
1.32
1.7
2.2
2.57
3.34
4.3
5.1

Heat output
at W10/
W35(2)
kW
10.1
12.9
16.7
19.6
25.8
33.3
39

Power consumption
kW
1.89
2.39
3.01
3.57
4.7
6.1
7.1

Performance factor
  5.34
5.4
5.55
5.49
5.49
5.46
5.49

Inside volume flow
m3/h
1.74
2.22
2.88
3.37
4.44
5.7
6.7

Outside volume flow
m3/h
1.77
2.26
2.94
3.45
4.54
5.85
6.8

Cooling output
at W30/
W7(5)
kW
9.1
11.2
14.2
16.3
22.4
28.4
32.6

Power consumption
kW
2.2
2.6
3.1
3.7
5.2
6.2
7.4

Performance factor
  4.14
4.31
4.58
4.41
4.31
4.58
4.41

Inside volume flow
m3/h
1.56
1.93
2.44
2.8
3.85
4.88
5.6

Outside volume flow
m3/h
1.94
2.37
2.98
3.44
4.74
5.95
6.88

Process medium
  Brine made from water with 33Vol.% ethylene glycol

Power
Type
Single or triple phase
Triple phase

Sound power level
dB(A)
46
47
48
48
49
49
49

(1)B0/W35=Brine water inlet temperature 0℃,heating flow 35℃

(2)W10/W35=Well water inlet temperature 10℃,heating flow 35℃

(3)Heating flow for 5K temperature span

(4)Heat source flow for 4K temperature span

(5)W25/W7=Outside water inlet temperature 25℃,cooling flow 7℃


Tags: ground    source    heat    pump   

Contact Information
Company Name:Guangzhou Hiseer Air Conditioning Co.,Ltd.
Contact Person:Jerry
City and Country:Guangzhou,China
Address:Huasheng Beiroad,Xicheng industry zone,Renhe town,Baiyun district,Guangzhou China.
Zip:510470
Email:jerry121@gmail.com
Telephone:86 20 61171400
Fax:86 20 61171400
MSN No:forward2012@yahoo.com.cn
Website:http://www.chinaheatpump.com     http://www.chinahiseer.com    

Company: Guangzhou Hiseer Air Conditioning Co.,Ltd.
Post Time: 2008-08-26 15:17Inquiry    reply quickly
Other TradeLeads
geothermal heat pump high temp ( 2008-08-26 15:15 )
geothermal heat pump ( 2008-08-26 15:07 )
heat pump with hot water ( 2008-08-26 15:00 )
Air souce heat pump ( 2008-08-26 14:45 )




Copyright ©TradeWebsites.net , 2006-2008 All Rights Reserved    Contact Us    Suggestion

粤ICP备06113501号